摘要:
当发生单相接地短路故障时,双馈感应发电机(DFIG)的暂态特性与普通的异步发电机有着较大区别.因此基于DFIG的暂态模型,采用对称分量法得到含撬棒电阻的正、负序等值电路,进而分析单相接地故障下,DFIG短路电流的瞬时值、最大值以及周期分量有效值的计算公式.最后对比PSCAD/EMTDC软件中的仿真结果,验证该文所推导出的单相接地故障下DFIG短路电流计算公式的准确性.
Abstract:
When the single-phase to ground fault occurs,the transient characteristics of the doubly fed induction generator (DFIG) are different from the common asynchronous generator.Therefore,in this paper,the positive and negative sequence equivalent circuit of DFIG with crowbar resistance was estimated by using the symmetrical component method on the basis of the DFIG transient model.Then the instantaneous maximum value and the effective value of the periodic component of DFIG short-circuit current were analyzed.Finally,the accuracy of the calculation formula of the DFIG single phase grounding fault proposed was verified in comparison with the simulation results of PSCAD/EMTDC.
作者 潘文霞 [1] 刘明洋 [1] 张艺博 [1] 杨刚 [1] 郭家圣 [1] 杨川 [2]
Author: Pan Wenxia[1] Liu Mingyang[1] Zhang Yibo[1] Yang Gang[1] Guo Jiasheng[1] Yang Chuan[2]
作者单位
  1. 河海大学能源与电气学院,南京,210098
  2. 国家电网公司扬州市供电公司,扬州,225000
期 刊: 太阳能学报 ISTIC EI SCI PKU CSSCI
Journal: Acta Energiae Solaris Sinica
年,卷(期) 2018, 39(1)
分类号 TM744
关键词: 双馈风电机组 知识脉络 短路电流 知识脉络 撬棒保护 知识脉络 对称分量法 知识脉络
Keywords: double fed wind turbine short circuit currents crowbar protection symmetrical component method
机标分类号
基金项目 国家自然科学基金,江苏高校优势学科建设工程